|
|
In a message dated 8/23/2005 8:48:05 A.M. Central Standard Time,
dfs155@adelphia.net writes:
Scott,
in the schematic submitted, can't for the life of me figure out why the
breaker (fuse?) that goes to the gear switch would be connected to the main
bus rather than the down-stream side of the 50 amp pump breaker. The way
it's shown, one would need to pull TWO breakers to positively safe
the system to do a proper emergency gear drop instead of just the one (you
want to de-energize the relays, since they're only for intermittent use, as
well as the main power to the pump circuit in case of a stuck relay,
right?).
In addition, there really needs to be a diode added to each
relay control terminal to ground (cathode to the terminal) or the pressure
switches and gear switch contacts will die an early death from the
inductive kick when the current to the relay coil is interrupted, e.g.,
relay is turned off. FWIW, the same is true of the starter relay, which is
identical to the pump relays, at least in my airplane.
As a firm
proponent of the KISS principal, especially for a system that is likely to
be needed while in a relatively high stress situation, having to remember
to pull just one breaker instead of two seems
preferable.
Dan,
Note that Bob's "just pull the relay breaker" is fine for testing (assuming
the system was wired the Lancair way). You are right that ultimately one
should be able to pull the motor breaker, too. KISS would imply that the
same method used for testing would be used in an emergency. Remember the
construction manual warning about not pulling both breakers.
Yes, you are right about the coil diodes (or MOVs, see Bob Nuckoll's
Aeroelectric web site) and I have them installed. It just seemed like
there wasn't room on the Lancair diagram for more stuff and I wanted to
emphasize the other, more severe issues.
KISS works for me.......
Scott Krueger
AKA Grayhawk Lancair N92EX IO320 SB 89/96 Aurora, IL
(KARR)
|
|