Mailing List lml@lancaironline.net Message #51635
From: <Sky2high@aol.com>
Sender: <marv@lancaironline.net>
Subject: Re: [LML] Re: Gear Relays are not working
Date: Sun, 31 May 2009 14:24:46 -0400
To: <lml@lancaironline.net>
Uh, a properly wired Oildyne pump has an internal thermal breaker.  I worry much more about shorting lines carrying potentially high amperage current.  If pump power were applied too long (more than 10 seconds, yellow transit light on, either up or down selected), I could always pull the breaker on my center console, just below my throttle wrist.  I never liked the other bad direction from Lancair - mounting the pump breaker on the baggage bulkhead (remember John Denver).  The instructions had it mounted there because it was a short run from the battery and master relay that was to be mounted back there also.  For me, it was natural to put the breaker on the center console since my battery and master relay is mounted behind the co-pilot seat, a mere 12 inches away.
 
Grayhawk 
 
In a message dated 5/28/2009 7:44:22 P.M. Central Daylight Time, snopercod@citcom.net writes:
Reply to Dan Schaefer:

No flames from me. Everything you said was correct, but I would like to
elaborate on a couple of your points.

In your home, the function of a circuit breaker is *only* to protect the
wiring, as you wrote. Your typical 20A circuit breaker will not protect
your garbage disposal from burning up if something gets jammed in there,
for example. That's why they have their own thermal circuit breakers
(that little red button down there). In an industrial setting,
thermal-magnetic circuit breakers are used to protect large motors, and
the 'heaters' are sized to protect the motor in case of a locked rotor.

It's my belief that the circuit breaker (or fuse) feeding the hydraulic
pump in the Lancair should be sized to protect the pump from burning up,
in addition to protecting the wiring, I believe that it *is* possible.

I have the specifications right here for the Oildyne (now Parker) Model
108AA19-AL-3VT as used in my Lancair 235. Unfortunately, it doesn't list
the locked-rotor current for the series-wound 12V DC motor. The chart in
there says that the motor draws ~15 Amps at low pressure, and about 40
Amps at 1500 PSI. It's my vague recollection that the locked-rotor
current for this motor is a little over 70 Amps, but I can't remember
where I came up with that. So just now, I did the best I could to
measure it by replacing the 40A Maxi-Fuse that I use to protect the
pump/wiring with 12" of 18AWG stranded wire as a 'shunt'. From wire
tables, the resistance of that piece of wire should be between .0055 and
.0065 ohms, but I have no way to measure it. Using my Fluke 87-V, the
'peak inrush' (250 uS) across the 'shunt' was 0.90V, the 100ms peak was
0.50V, and the voltage while the gear was coming up was ~0.30V. In
theory, the peak inrush should be the same as the locked-rotor current,
since both are measured with the motor not rotating.

Using the 6.0 ohms per 1000' average,  that works out to a peak inrush
of 150 amps, a 100ms peak of 83 Amps, and a transition current of 50
Amps. My gut tells me that those readings are too high by a factor of
two, so the resistance of my 'shunt' must be greater than I think it is
(* maybe not. See addendum). The point still remains, though, that the
current this motor will draw if something gets jammed in the gears is
roughly three times 'normal'. Whatever protection device you choose
should be sized to trip within a few seconds under those conditions.

(As a side note, while the inrush currents were the same in both
directions, the motor drew only 2/3 the current with the gear coming
'down' as it did coming 'up'. And if anybody was wondering, after five
gear cycles the piece of #18 AWG wire was warm to the touch, but not 'hot'.)

I'm attaching the time-current curves for a typical Klixon 7271 circuit
breaker. Per their specifications, the Klixon may never trip at all with
a 10% to 45% overload. With a 35 Amp breaker, that would mean the
hydraulic pump could draw from 38.5 to 50.75 Amps without the breaker
ever tripping. At a minimum, your wiring needs to be able to handle
that. AWG #10 would be a minimum, I think. With a locked rotor and
assuming the pump draws somewhere around 70 Amps (a 200% overload with a
35A breaker), the Klixon 7271 circuit breaker would trip anywhere
between 8 and 80 seconds. It's my belief that either the pump itself or
the wiring would burn up if the breaker took 80 seconds to trip. Data
for other Klixon models can be found at:
http://www.sensata.com/download/klixon-circuit-breaker-aircraft-catalog.pdf

Now looking at the Maxi-Fuse data at
http://www.littelfuse.com/data/en/Data_Sheets/299.pdf, I find that a 35
Amp Maxi-Fuse will open on a 200% overload between 6 and 40 seconds (20
seconds, on average), substantially faster than a similarly rated
circuit breaker. The 30 Amp Maxi-Fuse, if one chose to use that rating,
would open in less than ten seconds with a locked rotor.

The point of all this is that we builders should have some idea what the
hydraulic pump draws under what conditions, and the capabilities and
limitations of whatever device we choose to protect it and the wiring.
One advantage to using the Maxi-Fuse rather than the circuit breaker, is
that it allows the builder to experiment and find the proper rating for
his installation without having to rewire the panel.

*Addendum: In the link above, they listed the cold resistance of the 40A
Maxi-Fuse as 1.42 milli-ohms. So I installed one of those as a shunt and
re-did the test. I came up with similar (even higher) numbers than
before: 211/126/54 Amps. I guess my 'gut feeling' was wrong. Now I'm
going to have to buy a 200A shunt to verify all this. Nuts!




--
For archives and unsub http://mail.lancaironline.net:81/lists/lml/List.html
Image
tripcurve-7270.gif
Subscribe (FEED) Subscribe (DIGEST) Subscribe (INDEX) Unsubscribe Mail to Listmaster