To R. Dan Ribb, re: "Gear Electraulics" schematic.
Don't see anything to "rip you apart" about, though I do have a single
comment.
The breakers should be sized to protect the wires, rather than the circuit
component (you don't want a short in the wiring to cause a fire or burn up a
wire bundle - taking out other, uninvolved, circuits). As long as the
breaker ratings are sufficient to pass the current required by the circuit
without nuisance tripping but will trip on a short circuit, the wiring will
be protected.
Dan Schaefer
|
|