Kevin
writes: <<each time the gear motor runs, the output of the networked
sensors (GPS, EMS, and ADAHRS) gets interrupted, resulting in red X’s
displayed on screen. When the gear cycle is complete, the EFIS returns to
normal. Testing with the EFIS system power isolated from the aircraft's
electrical system by operating only on their independent backup batteries
resulted in the exact symptom.>
The problem
is likely NOT RF interference on the serial communication lines. The problem
likely IS poor ground wiring. The hydraulic pump draws a lot of amps. All
wire has resistance. Amps times resistance is volts so when the hydraulic
pump motor is running the "ground" at the battery and the
"ground" at the motor may be different by a several volts. Serial
(RS232) 1communication uses a single wire that transitions from one voltage
to another voltage to transmit data. The transmitter (sensor) and the
receiver (EFIS) compare the signal to the LOCAL ground. If the ground voltage
is different between the transmitter and the receiver then the signal may not
be received. For example, say the receiver transmits 4 volts as a binary
"1" and 1 volt as a binary "0" . The receiver interprets
anything less than 2.5 volts as a 0 and anything more than 2.5 volts as a 1.
If there is 2 volts of ground shift due to an induced voltage drop (the motor
running) then the receiver will "see" the incoming signal changing
from 3 volts to 6 volts, which it interprets as all 1s. A 1001101 transmitted
message would be received as 1111111. Not good.
Be sure that
your EFIS display and all the sensors get their power and ground from the
same point on the airframe. Good composite aircraft wiring systems have a
single point that is the ground reference with all component grounds coming
from this point. You do not want a ground wire run to another part of the
airframe and then branching to different devices as the resistance of the
wire will allow one device to effect the other. Power ground, signal ground
and shield grounds must all be tied to the same point or else you will induce
currents (AKA Ground Loops) in the ground wiring that will cause trouble.
Even if you
operate the EFIS off of emergency batteries, if a portion of the ground
wiring between the sensors and the EFIS share a ground path with the motor
then there will be trouble.
As my friend
Hamid Wasti says: "You must believe in one true Ground, because if you
don't, it will smite you!"
|