Mailing List lml@lancaironline.net Message #29524
From: Jeffrey Liegner, MD <liegner@earthlink.net>
Sender: Marvin Kaye <marv@lancaironline.net>
Subject: Pitot-Static Check...Repairman Certificate
Date: Sun, 17 Apr 2005 10:52:54 -0400
To: <lml@lancaironline.net>
Pitot-Static Check...Repairman Certificate
Can the person who holds the "Repairman " certificate for an experimental plane sign off on the Pitot-Static check, after confirming perfomrance (below) with a certified "IFR Box?"

Separate question...if the "IFR Box" is analog and the airspeed & altimeter in the plane are digital, and the analog output complies with the regs, but the more precise display shows bleed down of 3 knots per minute, is this out of specs?  Are their digital vs analog guage rules?

Jeff L
N334P




Test Airspeed and Altitude

Airspeed and altitude need to be tested using a Pitot/Static test set for proper  indications and values. Per FAR 43, Appendix E, the aircrafts' Pitot and Static  systems must be tested for leaks anytime a connection in the associated system  has been opened. This is done by applying pressure and vacuum to the Pitot and  Static systems respectively to a set point and noting the change after one minute  with the test box valves closed. Pitot System

1. Connect the Pitot/Static test set to the aircraft with approprate hoses and fittings.
2. Open the Pitot and Static bleed valves to equalize the pressure between the aircraft systems and the ambient air.
3. Close the Pitot (airspeed) bleed valve.
4. Open the Pitot pressure valve and apply enough pressure for the standby ASI and/or the  EFIS to display red line (Vne).
5. Close the Pitot pressure valve.
6. Start a timer and monitor any leakage of pressure during one minute.

NOTE: Airspeed should not drop more than 2 knots in a one minute time frame.  If the  leakage is more than 2 knots, tighten all Pitot fittings and test again. Repeat until pressure  drop is less than 2 knots per minute.

7. After leak test has been verified, open the Pitot bleed valve and vent the pressure until  the Pitot system has been equalized with the ambient air.

Static System

1. With the Pitot and Static system equalized, close the Static (altitude) bleed valve.
2. Set the pilot side EFIS baro scale to 29.92 (right knob adjsut).
3. Note the altitude reading.
4. Open the Static vacuum valve and apply enough vacuum for the EFIS to display one-thousand (1000) feet above the starting altitude.
5. Close the Static vacuum valve.
6. Start a timer and monitor any leakage of vacuum during one minute.

NOTE: Altitude should not drop more than 100 feet in a one minute time frame. If the  leakage is more than 100 feet, tighten all Static fittings and test again. Repeat until vacuum  leakage is less than 100 feet pre minute.

7. Open the Static bleed valve and vent the vacuum to equalize with ambient air.
8. Remove the hoses and fittings used to test the aircraft.

NOTE: During the leak tests, the EAU can be verified for proper airspeed, altitude, and  vertical speed readings. PITOT/STATIC CHECKLIST ? Pitot system leak less than 2 Kts/min and airspeed reading correct. ? Static system leak less than 100 ft/min and altimeter reading correct.

Subscribe (FEED) Subscribe (DIGEST) Subscribe (INDEX) Unsubscribe Mail to Listmaster